Prerequisites

Verify the OPC Server

To verify the OPC Server, on the machine where the DeltaV OPC Server is running, open DeltaV Explorer.

From the Applications menu, open Diagnostics.

image1.png

On the left side expand DeltaV System, Control Network and then the name of the DeltaV node. Select OPC Subsystem.

On the right, ensure that OInteg (Overall Integrity) is set to Good.

Verify the Data Retrieval

To verify data retrieval, use DeltaV’s OPCWatchIt application. To run, from the Windows search box, enter opcwatchit.

  1. Verify Server is set to OPC.DeltaV.1. If it is not, click Change Server to select it

  2. Click BrowsePath, select a tag and click OK

  3. Click Read to display real time value of the selected tag

If the OPC subsystem is not good or OPCWatchIt does not respond as described contact Emerson Automation Solutions technical support to troubleshoot and correct these issues.